Three kinds of power
- Real power (P), in watts, does the useful work: heat, light, motion.
- Reactive power (Q), in volt-amperes reactive (var), flows back and forth between the supply and the magnetic or electric fields of the load. It does no net work.
- Apparent power (S), in volt-amperes (VA), is the voltage multiplied by the current. It is what the cables and transformers must carry.
power factor = real power (W) ÷ apparent power (VA)
The three form a right-angled triangle, so S² = P² + Q². For clean sinusoidal waveforms the power factor equals the cosine of the phase angle between voltage and current, which is why it is often written cos φ.
Why it falls below 1
In a heater or an incandescent lamp, current rises and falls in step with voltage, and the power factor is 1. Motors, transformers and fluorescent ballasts contain coils whose magnetic fields make the current lag behind the voltage. The supply must deliver extra current that does no useful work. Electronic power supplies can lower the power factor in a different way, by drawing current in short pulses.
| Load | Typical power factor |
|---|---|
| Electric heater, kettle | 1.0 |
| Modern LED lamp with correction | 0.9 or higher |
| Induction motor, full load | 0.80 to 0.90 |
| Induction motor, lightly loaded | 0.2 to 0.5 |
| Uncorrected computer power supply | 0.6 to 0.7 |
kW and kVA
kW = kVA × power factor
A generator rated 100 kVA can supply 100 kW to heaters at power factor 1, but only 80 kW to motors at power factor 0.8. This is why generators, transformers and UPS units are rated in kVA: their limit is current, whatever the load does with it.
Worked example
A motor draws 10 A from a 230 V single-phase supply at a power factor of 0.85. Apparent power is 230 × 10 = 2,300 VA. Real power is 2,300 × 0.85 = 1,955 W. The remaining reactive power is √(2,300² − 1,955²) = 1,212 var.
Why it matters
A low power factor means more current for the same useful power. That brings larger cables, more heat lost in wiring and less spare capacity. Many electricity suppliers charge commercial customers for poor power factor. Households are normally billed only for real energy in kilowatt-hours.
Correcting it
Capacitors draw current that leads the voltage, the opposite of a motor. Connected alongside inductive loads, they supply the reactive power locally, so the supply no longer has to. Industrial sites install capacitor banks for this, and many electronic devices include active power factor correction circuits.
Frequently asked questions
What is a good power factor?
Utilities typically want commercial sites to stay above about 0.9 to 0.95. A value of 1.0 is ideal.
How do I convert kVA to kW?
Multiply by the power factor. With no other information, 0.8 is a common assumption for generators: 50 kVA × 0.8 = 40 kW.